Dold Liquid Level Relay - DIN Rail, 230 V ac 1

본 이미지는 참조용이오니 재확인이 필요하시면 문의해주세요.

대량 구매 할인 기용 가능

Subtotal (1 unit)*

₩285,854.00

Add to Basket
수량 선택 또는 입력
재고있음
  • 1 개 단위 배송 준비 완료
더 자세한 내용이 필요하신가요? 필요한 수량을 입력하고 '배송일 확인'을 클릭하면 더 많은 재고 및 배송 세부정보를 확인하실 수 있습니다.
수량
한팩당
1 - 4₩285,854.00
5 +₩273,314.40

* 참고 가격: 실제 구매가격과 다를 수 있습니다

RS 제품 번호:
465-0621
제조사 부품 번호:
MK9151N.12 2-450kOHM AC230V 0-20s
제조업체:
Dold
제품 정보를 선택해 유사 제품을 찾기
모두 선택

브랜드

Dold

Number of Inputs

1

Mounting Style

DIN Rail Mount

Probe Voltage

10V ac

Supply Voltage

230 V ac

Overall Length

90mm

Overall Width

22.5mm

Overall Depth

98mm

Minimum Operating Temperature

-20°C

Maximum Operating Temperature

+60°C

COO (Country of Origin):
DE

MK 9151N - level relay


Application


Level monitoring and control of conductive liquids and powders, e.g. maximum and minimum fill level, protection against overfilling and dry running
Monitoring and control of the mix ratio for conductive liquids
General resistance monitoring tasks, e.g. recording temperature limits with PTC
Contact protection relay with delay

Features


3 electrode connections for 2-point and 1-point level control
Measuring circuit for electrodes works on AC voltage generated internally in the device (approx. 30 Hz); therefore no electrolysis occurrence in the fluid
The measuring circuit galvanically isolated from the mains is immune from high levels of interference
Max. lead length to the electrodes: 3000 m
Wide setting range: 2 kΩ → 450 kΩ which enables differentiation between liquid and foam
Response and fallback delay: 0.2 s → 20 s, adjustable separately for MIN and MAX level
Programmable for operating or rest current principle
LEDs to indicate operational readiness and contact position
Output contact 2 changeovers
Overall width: 22.5 mm

Standards

  IEC/EN 60 255, DIN VDE 0435-303

Approvals

  CE


Liquid Level Relays are used to monitor the levels of conductive liquids, and are available in Up/Down, Minimum, Maximum, and Fill/Empty variations. Liquid Level Relays are straightforward to install and safe to use.


Application Examples


Liquid Level Relays (Conductive Level Sensors) are used in a wide variety of applications including waste water management and the monitoring and management of corrosive liquid media, and designed specifically to provide for the:


Monitoring and control of liquid levels
Protection of pumps against dry running
Ability to detect liquid leaks in a system
Control of media mixing ratios
Control of liquid levels

관련된 링크들