Dold Insulation Monitoring Relay, SPDT, 0.8 → 1.1 V, DIN Rail
- RS 제품 번호:
- 240-9049
- 제조사 부품 번호:
- AI898 DC24V 6kOhm UH=AC45-400Hz 230V
- 제조업체:
- Dold
Subtotal (1 unit)*
₩755,602.08
재고있음
- 1 개 단위 배송 준비 완료
더 자세한 내용이 필요하신가요? 필요한 수량을 입력하고 '배송일 확인'을 클릭하면 더 많은 재고 및 배송 세부정보를 확인하실 수 있습니다.
수량 | 한팩당 |
|---|---|
| 1 + | ₩755,602.08 |
* 참고 가격: 실제 구매가격과 다를 수 있습니다
- RS 제품 번호:
- 240-9049
- 제조사 부품 번호:
- AI898 DC24V 6kOhm UH=AC45-400Hz 230V
- 제조업체:
- Dold
사양
참조 문서
제정법과 컴플라이언스
제품 세부 사항
제품 정보를 선택해 유사 제품을 찾기
모두 선택 | 제품 정보 | 값 |
|---|---|---|
| 브랜드 | Dold | |
| Monitoring Application | Insulation | |
| Voltage Sensing Range | 0.8 → 1.1 V | |
| Contact Configuration | SPDT | |
| Mounting Type | DIN Rail | |
| Time Delay | 0.4s | |
| Series | AI 898 | |
| Operating Temperature Range | +60°C | |
| Width | 45mm | |
| Maximum Operating Temperature | +60°C | |
| Dimensions | 115 x 45 x 77mm | |
| Length | 115mm | |
| Minimum Operating Temperature | -20°C | |
| Height | 77mm | |
| 모두 선택 | ||
|---|---|---|
브랜드 Dold | ||
Monitoring Application Insulation | ||
Voltage Sensing Range 0.8 → 1.1 V | ||
Contact Configuration SPDT | ||
Mounting Type DIN Rail | ||
Time Delay 0.4s | ||
Series AI 898 | ||
Operating Temperature Range +60°C | ||
Width 45mm | ||
Maximum Operating Temperature +60°C | ||
Dimensions 115 x 45 x 77mm | ||
Length 115mm | ||
Minimum Operating Temperature -20°C | ||
Height 77mm | ||
- COO (Country of Origin):
- DE
Insulation monitor for direct current networks, AI898
Fixed response time 6 kΩ
LED display for operational readiness and earth fault
1 changeover
Overall width 45 mm
LED display for operational readiness and earth fault
1 changeover
Overall width 45 mm
The AI898 insulation monitor displays the insulation resistance of unearthed direct current networks to earth. It does not detect symmetrical earth faults. In practice, these faults are generally insignificant.
The AI898 works on the quiescent current principle, for example when the auxiliary voltage is applied to terminals A1 → A2 the output relay is activated and the "ON" LED indicates that the insulation resistance RAN is not less than the minimum value. If insulation resistance falls below the response value, the output relay drops, the "ON" LED goes out and the second LED for "Earth fault" lights up.
A bridge between terminals LT1 and LT2 (inserted as standard) allows the AI898 to be programmed for memory storage behaviour; remove the bridge to programme hysteresis behaviour. The bridge can be replaced with a delete key with an NC contact. A test key (PT) tests the functional efficiency of the device (as per VDE 0435).
The AI898 works on the quiescent current principle, for example when the auxiliary voltage is applied to terminals A1 → A2 the output relay is activated and the "ON" LED indicates that the insulation resistance RAN is not less than the minimum value. If insulation resistance falls below the response value, the output relay drops, the "ON" LED goes out and the second LED for "Earth fault" lights up.
A bridge between terminals LT1 and LT2 (inserted as standard) allows the AI898 to be programmed for memory storage behaviour; remove the bridge to programme hysteresis behaviour. The bridge can be replaced with a delete key with an NC contact. A test key (PT) tests the functional efficiency of the device (as per VDE 0435).
관련된 링크들
- Dold Insulation Monitoring Relay, 1, 3 Phase, SPDT, 0.8 → 1.1 V, DIN Rail
- Dold Frequency Monitoring Relay, SPDT, DIN Rail
- Dold Insulation Monitor, 400 → 600V ac/dc, DIN Rail
- Dold Insulation Monitoring Relay, 1, 3 Phase, SPDT, 0 → 500V ac, DIN Rail
- Dold Cycle Monitoring Relay, SPDT, 230V ac, DIN Rail
- Dold Insulation Monitoring Relay, 1, 3 Phase, DPDT, 0 → 500V ac, DIN Rail
- Dold Speed Monitoring Relay, SPDT, DIN Rail
- Dold Thermistor Motor Protection Monitoring Relay, SPDT, DIN Rail