Fluke 1623-2 CAT II 300V

Subtotal (1 unit)*

₩5,373,792.00

Add to Basket
수량 선택 또는 입력
제한된 재고
  • 추가로 2026년 3월 30일 부터 4 개 단위 배송
더 자세한 내용이 필요하신가요? 필요한 수량을 입력하고 '배송일 확인'을 클릭하면 더 많은 재고 및 배송 세부정보를 확인하실 수 있습니다.
수량
한팩당
1 +₩5,373,792.00

* 참고 가격: 실제 구매가격과 다를 수 있습니다

RS 제품 번호:
798-3965
Distrelec 제품 번호:
110-79-080
제조사 부품 번호:
FLUKE-1623-2 KIT
제조업체:
Fluke
제품 정보를 선택해 유사 제품을 찾기
모두 선택

브랜드

Fluke

Measurement Type

Earth Resistance

Includes

Batteries, Cable Reel, Carrying Case, User Manual

Model Number

1623-2

Safety Category Voltage

300V

Width

187mm

Safety Category Level

CAT II

제외

COO (Country of Origin):
RO

Fluke Earth Tester Kit, 19.99kΩ Maximum Resistance Measurement, ±2% rdg + 3 Digits Accuracy - FLUKE-1623-2 KIT


This earth tester kit is a battery-powered instrument for measuring ground and earth loop resistance in utility, industrial and maintenance settings. It performs 3- and 4-pole fall-of-potential and soil resistivity tests, selective and stakeless clamp-based checks, and stores results for USB download. The unit is designed for outdoor use and portable field work, supplied with accessories for comprehensive site testing.

Features & Benefits


• Measures up to 19.99kΩ for broad resistance range
• LCD display with 1999-digit visibility for clear readings
• Internal memory holds up to 1500 records for data capture
• IP56 protection for use in dusty or wet conditions
• Battery life greater than 3000 measurements with AA alkaline cells
• Stakeless testing with two clamps to save setup time

Applications


• Suitable for fault-to-earth impedance assessment in substations
• Ideal for site surveys where stake placement is impractical
• Used for soil resistivity mapping during earthing design
• Can be used for selective testing of individual earthing rods
• Suitable for routine maintenance checks in industrial plants

How does the instrument handle interference from nearby electrical systems?


It includes frequency selection and automatic frequency control to identify and avoid interfering signals and minimise measurement error.

What safety classification applies when working near live equipment?


The instrument meets CAT II 300V limits for external voltage conditions and provides double or reinforced insulation with measurement inhibited above safe thresholds.

What data transfer options are available for job reporting?


Test results are stored in internal memory and can be exported via the USB port for analysis and Record keeping.

How is stakeless measurement performed without disconnecting the earthing system?


One clamp injects a known AC voltage while a second clamp measures current, allowing closed-loop resistance determination without removing bonds.

Supplied with

1623-2 GEO Earth Ground Tester, user manual, batteries, quick reference guide, USB cable, 2 clamps, C1620 carrying case, 4 earth ground stakes and 3 cable reels

관련된 링크들