The universal KS 50-1 temperature controller is intended for precise and cost-effective control tasks. The instrument provides simple 2-point (on/off) control, continuous PID control or 3-point stepping control. The process value signal is connected via a universal input. A supplementary analog input can be used for heating current measurement or as an external set-point input.
The KS 50-1 has three process outputs that can be 3 relays or 2 relays plus a universal output. This universal output can be used for operating a solid-state relay, a continuous current/voltage output or to energize a two-wire transmitter. Optionally there are two additional optocoupler outputs that can be used freely.
The controller is suitable for a number of industry applications including: Furnaces and ovens, Burners and boilers, Plastics processing, Hot runners, Driers, Climatic chambers & Heat treatment plants.
• Universal continuous/switching version, i.e. reduced stocks • 100ms cycle time, i.e. also suitable for fast control loops • 20ms as shortest pulse for very fast / strong actuators • Freely configurable analog output, e.g. as process value output • Customer-specific linearisation for all sensors • Settings can be blocked via password and internal switch for high security • Extended temperature range up to 60 °C allows mounting close to the process • Easy 2-point or offset measurement correction • Emergency operation after sensor break by means of the "output hold" function • Logical combination of digital outputs, e.g. for general alarm • Programmer with 10 segments and "end" signal • RS 422/485 Modbus RTU interface • Built-in transmitter power supply • Splash-water proof front (IP65)
Supplied with
German Manual
PMA Temperature Controllers
속성
값
Output Type
Relay
Supply Voltage
90 → 250 V ac
Size
96 x 48 (1/8 DIN)mm
Number of Outputs
2
Minimum Operating Temperature
-20°C
Maximum Operating Temperature
+65°C
Temperature Range
0 → +1760 (Type R Thermocouple) °C, 0 → +1760 (Type S Thermocouple) °C, -100 → +1200 (Type J Thermocouple) °C, -100 → +1300 (Type N Thermocouple) °C, -100 → +1350 (Type K Thermocouple) °C, -100 → +900 (Type L Thermocouple) °C, -200 → +200 (PT1000) °C, -200 → +850 (PT100) °C, -50 → +150 (KTY 11-6) °C