Omron G9SA, 100V ac, 240 V ac Safety Relay, 5 Safety Contacts, 1

본 이미지는 참조용이오니 재확인이 필요하시면 문의해주세요.

Subtotal (1 unit)*

₩791,560.00

Add to Basket
수량 선택 또는 입력
일시적 품절
  • 2026년 12월 24일 부터 배송
더 자세한 내용이 필요하신가요? 필요한 수량을 입력하고 '배송일 확인'을 클릭하면 더 많은 재고 및 배송 세부정보를 확인하실 수 있습니다.
수량
한팩당
1 +₩791,560.00

* 참고 가격: 실제 구매가격과 다를 수 있습니다

RS 제품 번호:
757-9323
제조사 부품 번호:
G9SA-501 AC100-240
제조업체:
Omron
제품 정보를 선택해 유사 제품을 찾기
모두 선택

브랜드

Omron

Product Type

Safety Relay

Safety Contacts

5

Contact Configuration

3PST

Number of Auxiliary Contacts

1

Reset Method

Automatic & Manual

Mount Type

DIN Rail

Series

G9SA

Power Consumption

11VA

Terminal Type

Screw

Switching AC Voltage

240V ac

Minimum Operating Temperature

-25°C

Standards/Approvals

EN, UR, CSA

Switching DC Voltage

24V dc

Contact Current

5A

Maximum Operating Temperature

55°C

Height

111mm

Length

94mm

Width

45mm

Hazardous Area Certification

No

Safety Category

4

Coil Voltage

100V ac, 240V ac

COO (Country of Origin):
CN

Omron G9SA Series Safety Relay, 100/240V Coil Voltage, 5A Contact Current - G9SA-501 AC100-240


This safety relay is a Compact control unit designed to monitor and switch safety circuits in industrial environments. It accepts a broad supply range and provides multiple safety outputs and auxiliary contact functionality, enabling integration with standard safety sensors, two-hand controllers and expansion units for machine-protection systems.

Features & Benefits


• 100 to 240 V AC supply minimises inventory and simplifies installation
• Five safety contacts allow multiple load switching at 5A
• 3PST main contact configuration supports independent control paths
• 11VA power consumption for 100–240 V operation reduces supply loading
• Screw terminals with 0.98N·m torque rating ensure secure connections

**Applications**


• Suitable for emergency-stop circuit control in factory machinery
• Ideal for integration with PNP OSSD safety sensors and area scanners
• Used with two-hand control stations complying with EN574
• Can be used for motor contactor interlocking in production lines
• Suitable for systems requiring DIN-rail or screw mounting versatility

What environments can it operate in regarding temperature and humidity?


It operates between -25°C to 55°C with 35% to 85% relative humidity when free of icing or condensation.

How does the device behave after a fault that clears?


Reset can be set to automatic or manual, and an earth-short thermistor enables automatic reset when a earth fault is cleared.

What electrical isolation and endurance characteristics should I expect?


Dielectric strength between outputs is 2,500 V AC for 1 min and electrical life is rated at 100,000 operations at approx.1,800 operations/hr.

How are expansion and off-delay functions handled?


Modular expansion units connect via a dedicated connector and off-delay models provide selectable timings up to 30s across predefined steps.

Approvals

UL, CSA

Standards

EN954-1, EN60204-1, EN574 (-TH301), UL508, CSA C22.2 No. 14