Unipower 40A HPL Motor Load Monitor, 100V ac, 400 V ac, 50 °C, -15 °C

Subtotal (1 unit)*

₩1,079,300.00

Add to Basket
수량 선택 또는 입력
재고있음
  • 추가로 2026년 11월 23일 부터 10 개 단위 배송
  • 추가로 2026년 11월 25일 부터 5 개 단위 배송
더 자세한 내용이 필요하신가요? 필요한 수량을 입력하고 '배송일 확인'을 클릭하면 더 많은 재고 및 배송 세부정보를 확인하실 수 있습니다.
수량
한팩당
1 +₩1,079,300.00

* 참고 가격: 실제 구매가격과 다를 수 있습니다

RS 제품 번호:
745-8030
제조사 부품 번호:
HPL500
제조업체:
Unipower
제품 정보를 선택해 유사 제품을 찾기
모두 선택

브랜드

Unipower

Product Type

Motor Load Monitor

Current Rating

40A

Motor Protection Component

Load Monitor

Supply Voltage

100V ac, 400V ac

Series

HPL

Sensing Type

Current Transformer

Overall Length

75mm

Overall Width

56mm

Overall Depth

110mm

IP Rating

IP20

Minimum Operating Temperature

-15°C

Maximum Operating Temperature

50°C

Standards/Approvals

No

COO (Country of Origin):
DK

HPL500 Digital Motor Load Monitor


The HPL500 replaces the HPL420 and also incorporates many new features, however it has been designed so that users of the HPL420 will be familiar with its set-up procedure. The display is used as a reference enabling true motor load, trip levels and all other variables to be displayed and programmed quickly and accurately using only three push buttons. For two speed motor applications an input allows the application to select the active limit

The HPL500 is usually mounted in the motor control panel and is connected to a convenient point on the motor supply (before Inverter - if used).

Therefore no external field wiring or sensors in the equipment are necessary. In addition to displaying true motor power in real time the units capture and, on demand, display the instantaneous minimum and maximum power levels to assist in setting up trip limits and fault diagnosis. The HPL500 features a current feed-through tube for measuring continuous motor currents up to 40 amps, (27.7kW at 3 x 400vac). Therefore no Current Transformer is required unless the motors continuous current exceeds 40A.

A specially designed power supply (Patent Pending) allows the motor voltage to be programmable from 100 – 400vac single phase and 100 – 575vac 3-phase making the HPL500 suitable for world-wide use.

The 0(4)-20ma analogue output, which is proportional to motor load, can be scaled to the range of measured power and can be inverted for use in closed loop control systems.

Measures true motor load in kW (√3 x I x V x Cosφ) and futures a digital display of kW% and kW, and programmable trips for over and/or under load events

Can be programmed to calculate Shaft Output Power P2 if required

Protects equipment from damage caused by the motor running against a jam, blockage or under load

Used in processes to trigger actions when predetermined load levels are reached (end point monitoring)

Three digital delay timers, programmable from 0.1-99.9 seconds are incorporated to time out motor start surge and short duration over and under power events which could cause nuisance tripping

Two output relays are individually programmable, over or under-load alarms

Output relay state (NO or NC) can also be programmed

All settings are key-lock protected

Used for the over/under load protection of: Pumps (dry run, closed valve), Fans (broken belt, closed damper), Conveyors (screw and belt) Separation screens, Macerators, Scrapers, Mechanical drives (gearboxes, chains)

Also suitable for Process Control, PLC and SCADA input

Approvals

CE, UL and GOST-R