Fluke 1555 Insulation Resistance Tester, 250V Min, 10000V Max, 2TΩ Max, CAT III 1000 V, CAT IV 600 V
- RS 제품 번호:
- 705-1963
- 제조사 부품 번호:
- 3665111
- 제조업체:
- Fluke
사용할 수 없음
RS는 더 이상 이 제품을 입고하지 않습니다.
- RS 제품 번호:
- 705-1963
- 제조사 부품 번호:
- 3665111
- 제조업체:
- Fluke
사양
참조 문서
제정법과 컴플라이언스
제품 세부 사항
제품 정보를 선택해 유사 제품을 찾기
모두 선택 | 제품 정보 | 값 |
|---|---|---|
| 브랜드 | Fluke | |
| Model Number p | 1555 | |
| Tester Type | Insulation Resistance Tester | |
| Maximum Test Voltage | 10000V | |
| Minimum Test Voltage | 250V | |
| Maximum Insulation Resistance Measurement | 2TΩ | |
| Display Type | LCD | |
| Test Current | 1 nA → 2 mA | |
| Battery Life | 750 Tests | |
| Power Source | Battery | |
| Battery Type | Rechargeable Lead Acid (Yuasa NP2.8-12) | |
| Minimum Operating Temperature | -20°C | |
| Maximum Operating Temperature | +50°C | |
| Safety Category | CAT III 1000 V, CAT IV 600 V | |
| Safety Category Voltage | 600 V, 1000 V | |
| Safety Category Level | CAT III, CAT IV | |
| Dimensions | 277 x 269 x 160mm | |
| Length | 277mm | |
| Width | 269mm | |
| Weight | 3.7kg | |
| Height | 160mm | |
| 모두 선택 | ||
|---|---|---|
브랜드 Fluke | ||
Model Number p 1555 | ||
Tester Type Insulation Resistance Tester | ||
Maximum Test Voltage 10000V | ||
Minimum Test Voltage 250V | ||
Maximum Insulation Resistance Measurement 2TΩ | ||
Display Type LCD | ||
Test Current 1 nA → 2 mA | ||
Battery Life 750 Tests | ||
Power Source Battery | ||
Battery Type Rechargeable Lead Acid (Yuasa NP2.8-12) | ||
Minimum Operating Temperature -20°C | ||
Maximum Operating Temperature +50°C | ||
Safety Category CAT III 1000 V, CAT IV 600 V | ||
Safety Category Voltage 600 V, 1000 V | ||
Safety Category Level CAT III, CAT IV | ||
Dimensions 277 x 269 x 160mm | ||
Length 277mm | ||
Width 269mm | ||
Weight 3.7kg | ||
Height 160mm | ||
- COO (Country of Origin):
- US
Fluke 1550, 1555 5kV and 10kV Insulation Tester
High voltage insulation tester ideal for testing high voltage equipment including switchgear, motors, generators and cables.
Meets requirements of IEEE 43-2000
Capacitance and leakage current measurement
Resistance measurements up to 2TΩ (Fluke 1555)
Ramp function for breakdown testing
Voltage breakdown detection alerts and voltage reading up to 600 V ac or dc for increased user safety
99 measurements storage and recall and PC interface
Automatic calculation of Dielectric Absorption (DAR) and Polarization Index (PI)
Timer settings up to 99 minutes for timed tests
Guard system eliminates the effect of surface leakage current on high-resistance measurements
Large LCD display with analogue bargraph
Long life lead acid battery with over 750 tests between charges
EN 61010 safety rating CAT IV 1000 V, CAT III 1000 V
Meets requirements of IEEE 43-2000
Capacitance and leakage current measurement
Resistance measurements up to 2TΩ (Fluke 1555)
Ramp function for breakdown testing
Voltage breakdown detection alerts and voltage reading up to 600 V ac or dc for increased user safety
99 measurements storage and recall and PC interface
Automatic calculation of Dielectric Absorption (DAR) and Polarization Index (PI)
Timer settings up to 99 minutes for timed tests
Guard system eliminates the effect of surface leakage current on high-resistance measurements
Large LCD display with analogue bargraph
Long life lead acid battery with over 750 tests between charges
EN 61010 safety rating CAT IV 1000 V, CAT III 1000 V
Supplied with
Test cables & crocodile clips, infrared USB adaptor, AC power cord, 12V lead acid battery (fitted), FlukeView Forms Basic Software, user manual on CD-ROM, soft carrying case (Fluke 1555 only)
Fluke 1550 & 1555 kits include: IP67 hard case, NIST traceable certificate of calibration and additional ruggedized crocodile clips
Fluke 1550 & 1555 kits include: IP67 hard case, NIST traceable certificate of calibration and additional ruggedized crocodile clips
관련된 링크들
- Fluke 1555 FC Insulation Tester, 250 V Min, 10000 V Max, 2 TΩ CAT IV, CAT III
- Fluke 1587 Insulation Resistance Tester, 50V Min, 1000V Max, 2GΩ Max, CAT III 1000 V, CAT IV 600 V
- Fluke 1550C Insulation Tester, 250 V Min, 5000 V Max CAT IV, CAT III
- Fluke 1587 Insulation Tester, 50 V Min, 1000 V Max CAT IV, CAT III
- Fluke 1507 Insulation Tester, 50 V Min, 1000 V Max, 10 GΩ CAT III, CAT IV
- Fluke 1577 Insulation Tester, 500 V Min, 1000 V Max, 2 GΩ CAT III, CAT IV
- Fluke 1503 Insulation Tester, 500 V Min, 1000 V Max, 2000 mΩ CAT IV, CAT III
- Fluke 1550C FC Insulation Tester, 250 V Min, 5000 V Max CAT III, CAT IV