ABB Auxiliary Contact, 4 Contact, 3 NO/1 NC, CA4, Front, 6 A, 600 V dc, 690V ac, 1SBN010140R1331 CA4-31U

Subtotal (1 unit)*

₩41,840.00

Add to Basket
수량 선택 또는 입력
재고있음
  • 추가로 2026년 10월 12일 부터 17 개 단위 배송
더 자세한 내용이 필요하신가요? 필요한 수량을 입력하고 '배송일 확인'을 클릭하면 더 많은 재고 및 배송 세부정보를 확인하실 수 있습니다.
수량
한팩당
1 +₩41,840.00

* 참고 가격: 실제 구매가격과 다를 수 있습니다

RS 제품 번호:
711-6373
제조사 부품 번호:
1SBN010140R1331 CA4-31U
제조업체:
ABB
제품 정보를 선택해 유사 제품을 찾기
모두 선택

브랜드

ABB

Number of Contacts

4

Product Type

Auxiliary Contact

Normal State Configuration

3 NO/1 NC

Series

CA4

Contact Current

6A

Mount Type

Front

Terminal Type

Screw

Pole and Throw Configuration

4

Contact Voltage

600V dc, 690V dc

Operational Current Ie

6A

Mechanical Durability

10Mcycles

Rated Insulation Voltage Ui

690V

Mounting Location

Front Side

Minimum Operating Temperature

-40°C

Maximum Operating Temperature

70°C

Standards/Approvals

No

ABB CA4 Series Auxiliary Contact, 6A Operational Current, 690V Rated Insulation Voltage - 1SBN010140R1331 CA4-31U


This auxiliary contact provides additional switching contacts for contactor control circuits in industrial electrical systems. It mounts on the front side of compatible contactors and supplies instantaneous changeover contacts for signalling, interlock or auxiliary control functions in automation and electrical installations.

Features & Benefits


• 4-pole configuration delivering versatile auxiliary switching capability
• 3NO1NC arrangement supplying both make and break contacts
• Rated for 6A continuous switching to support control circuits
• Insulation rating 690VUi enabling high-voltage auxiliary use
• Mechanical endurance rated at 10Mcycles for long service life
• Operates across −40°C to 70°C for wide ambient tolerance

**Applications**


• Suitable for retrofitting control panels requiring additional contacts
• Used with AF09–AF16 contactors to extend auxiliary functions
• Ideal for signalling and interlocking in automation systems
• Can be used for DC control circuits up to 600V in select installations

How are electrical connections MADE to the unit?


Connections use screw terminals compatible with flexible and rigid conductors including ferrules specified for 0.75–2.5mm² and 1–2.5mm² ranges.

What switching duty can be expected for AC control applications?


AC-15 operational currents vary by voltage

typical values include 6A at 24/127V, 4A at 220/240V and 3A at 400/440V for control loads.

Which contactor installation location is required for fitting?


It is designed for front mounting on the contactor body and aligns with Terminal markings for three-pole contactors.

What short-time withstand capability does it offer?


The unit supports short-time currents such as 140A for 0.1s and 100A for 1s in auxiliary circuits.

What level of protection do the terminals provide?


Auxiliary terminals are rated to IP20 in accordance with relevant enclosure standards.

Standards

UL 508, CSA C22.2 N14

관련된 링크들