사양
참조 문서
제정법과 컴플라이언스
제품 세부 사항
제품 정보를 선택해 유사 제품을 찾기
모두 선택 | 제품 정보 | 값 |
|---|---|---|
| 브랜드 | Phoenix Contact | |
| Product Type | Galvanic Barrier | |
| Number of Channels | 2 | |
| Barrier Type | Galvanic Barrier | |
| Mount Type | DIN Rail | |
| Hazardous Area Certification | No | |
| Terminal Type | Push-in | |
| Supply Voltage | 19.2, 30V dc | |
| IP Rating | IP20 | |
| Minimum Operating Temperature | -20°C | |
| Maximum Safety Current | 10.3mA | |
| Signal Type | Digital | |
| Maximum Safety Voltage | 125, 253V dc | |
| Maximum Operating Temperature | 60°C | |
| Standards/Approvals | RoHS, ATEX, IEC, UL, CE, WEEE | |
| Series | MACX MCR-EX-SL-2NAM | |
| 모두 선택 | ||
|---|---|---|
브랜드 Phoenix Contact | ||
Product Type Galvanic Barrier | ||
Number of Channels 2 | ||
Barrier Type Galvanic Barrier | ||
Mount Type DIN Rail | ||
Hazardous Area Certification No | ||
Terminal Type Push-in | ||
Supply Voltage 19.2, 30V dc | ||
IP Rating IP20 | ||
Minimum Operating Temperature -20°C | ||
Maximum Safety Current 10.3mA | ||
Signal Type Digital | ||
Maximum Safety Voltage 125, 253V dc | ||
Maximum Operating Temperature 60°C | ||
Standards/Approvals RoHS, ATEX, IEC, UL, CE, WEEE | ||
Series MACX MCR-EX-SL-2NAM | ||
- COO (Country of Origin):
- DE
Phoenix Contact Galvanic Barrier, 10.3mA Maximum Current, 19.2V to 30V Supply Voltage - MACX MCR-EX-SL-2NAM-T-SP - 2924090
To ensure the safe operation of your commercial and industrial applications, use this galvanic barrier from Phoenix Contact. It allows for power transfers between circuits that mustn't be connected. To allow energy to flow through a field and not the electrical connections, it breaks ground loops and separates the input and output supplies to a device. This prevents unwanted current from flowing between two units sharing a ground conductor to avoid damage and injury caused by electrical shocks. Use this device to operate proximity sensors and switches in areas where explosive atmospheres are present.
Passive transistor outputs transmit signals to the safe area so that current doesn't ground itself through a user's body. Line fault detection (LFD) via a colour-coded green, yellow and red LED display helps you pinpoint and fix problems in a circuit to promote workplace safety and avoid production downtime. Digital input provides a practical way of isolating and communicating signals.
• Conformitè Europëenne (CE) compliance means the product meets European health, safety and environmental standards
• Meets RoHS (Restriction of Hazardous Substances) standards, meaning the product contains only trace amounts of any dangerous materials
• Wide operating temperatures from -20°C to +60°C for use in demanding environments
Ex-i NAMUR Isolating Amplifier, 2-channel, transistor outputs
For operating proximity sensors and switches in Ex areas
The signals are transmitted via transistor outputs (passive) to the safe area. Line fault detection (LFD), 3-way isolation, SIL 2
Group and Category
EN 61326, ATEX II (1) GD [Ex ia] IIC, [Ex ia] IIC; [Ex iaD]; Ex nA II T4 X, SIL 2 according to EN 61508, CUL Listed, UL Listed, IECEx, UL-EX LIS / CUL-EX LIS.
Approvals
CE-compliant
관련된 링크들
- Phoenix Contact 2 Channel Galvanic Barrier, Digital, ATEX
- Phoenix Contact Galvanic Barrier, Digital, ATEX
- Phoenix Contact 2 Channel Galvanic Barrier, ATEX
- Phoenix Contact 2 Channel Galvanic Barrier, Analogue, ATEX
- Turck 2 Channel Galvanic Barrier, Digital, IECEx/ATEX
- Phoenix Contact Galvanic Barrier, ATEX
- Phoenix Contact Galvanic Barrier, Analogue, ATEX
- JM CONCEPT 2 Channel Galvanic Barrier