Better World
Siemens Residual Current Circuit Breaker with Overload Protection, 13 A Current Rating, 2-Pole, 30 mA Trip Sensitivity,
- RS 제품 번호:
- 187-3288
- Distrelec 제품 번호:
- 301-49-285
- 제조사 부품 번호:
- 5SV1316-7KK13
- 제조업체:
- Siemens
Subtotal (1 unit)*
₩149,685.60
재고있음
- 61 개 단위 배송 준비 완료
더 자세한 내용이 필요하신가요? 필요한 수량을 입력하고 '배송일 확인'을 클릭하면 더 많은 재고 및 배송 세부정보를 확인하실 수 있습니다.
수량 | 한팩당 |
|---|---|
| 1 + | ₩149,685.60 |
* 참고 가격: 실제 구매가격과 다를 수 있습니다
Better World
Our Better World range features products that make it easy for you to make a greener product choice you can trust. Click here to find out more.
- RS 제품 번호:
- 187-3288
- Distrelec 제품 번호:
- 301-49-285
- 제조사 부품 번호:
- 5SV1316-7KK13
- 제조업체:
- Siemens
사양
참조 문서
제정법과 컴플라이언스
제품 세부 사항
제품 정보를 선택해 유사 제품을 찾기
모두 선택 | 제품 정보 | 값 |
|---|---|---|
| 브랜드 | Siemens | |
| Product Type | Residual Current Circuit Breaker with Overload Protection | |
| Current Rating | 13 A | |
| Series | 5SV1316 | |
| Range | SENTRON | |
| Number of Poles | 2 | |
| Trip Sensitivity | 30mA | |
| Tripping Characteristics | Type C | |
| Mount Type | DIN Rail | |
| Rated AC Voltage | 195 V ac | |
| Terminal Type | Screw | |
| Earth Leakage Protection Type | Type A | |
| Width | 18 mm | |
| Height | 90mm | |
| Depth | 77mm | |
| Better World Product | Yes | |
| Better World Claim | Concentrated or Compact Solution, Extended Product Life, Low Carbon Manufacture | |
| Standards/Approvals | No | |
| Breaking Capacity | 6kA | |
| 모두 선택 | ||
|---|---|---|
브랜드 Siemens | ||
Product Type Residual Current Circuit Breaker with Overload Protection | ||
Current Rating 13 A | ||
Series 5SV1316 | ||
Range SENTRON | ||
Number of Poles 2 | ||
Trip Sensitivity 30mA | ||
Tripping Characteristics Type C | ||
Mount Type DIN Rail | ||
Rated AC Voltage 195 V ac | ||
Terminal Type Screw | ||
Earth Leakage Protection Type Type A | ||
Width 18 mm | ||
Height 90mm | ||
Depth 77mm | ||
Better World Product Yes | ||
Better World Claim Concentrated or Compact Solution, Extended Product Life, Low Carbon Manufacture | ||
Standards/Approvals No | ||
Breaking Capacity 6kA | ||
- COO (Country of Origin):
- RO
Siemens 5SV1316 Series Residual Current Circuit Breaker with Overload Protection, 13A Current, 30mA Trip Sensitivity - 5SV1316-7KK13
This residual current circuit-breaker with overload protection provides combined earth-fault detection and overcurrent interruption for single-phase installations. Designed for DIN-rail fitting in distribution boards, it protects circuits by disconnecting on residual currents and instantaneous overloads while supporting AC supply systems at 230V and 50 Hz.
Features & Benefits
• Type A detection with 30 mA sensitivity for AC and pulsating faults
• 6 kA breaking capacity to limit fault energy and damage
• Type C instantaneous tripping for moderate inrush current tolerance
• Two-pole design enabling simultaneous live and NEUTRAL switching
• Screw terminals accepting up to 16mm² for robust conductor connections
• Compact width of 18mm conserving panel space
• 6 kA breaking capacity to limit fault energy and damage
• Type C instantaneous tripping for moderate inrush current tolerance
• Two-pole design enabling simultaneous live and NEUTRAL switching
• Screw terminals accepting up to 16mm² for robust conductor connections
• Compact width of 18mm conserving panel space
Applications
• Suitable for residential distribution boards requiring earth-leakage protection
• Ideal for small commercial installations with single-phase circuits
• Used for protecting lighting and socket circuits with moderate inrush currents
• Can be used for retrofit projects where DIN-rail mounting is required
• Ideal for small commercial installations with single-phase circuits
• Used for protecting lighting and socket circuits with moderate inrush currents
• Can be used for retrofit projects where DIN-rail mounting is required
What is the expected mechanical service life under normal switching?
The device is rated for approximately 10,000 switching cycles in typical mechanical operation.
How does ambient temperature affect rated current-carrying capability?
The rated 13A current is derated progressively with temperature, for example to about 12.35A at 40 °C and to about 10.01A at 70 °C.
What installation orientations and clearances are supported?
It may be mounted in any position on a standard DIN rail and offers IP20 protection when installed with conductors connected inside a distribution enclosure.
Which surge and switching performance figures are relevant for coordination?
Surge resistance is about 1 kA for an 8/20 μs waveform and switching capacities include 6 kA per EN 60898 and 15 kA per IEC 60947-2.
What conductor preparations and tightening parameters are required?
Stranded conductors up to 16mm² and finely stranded with ferrules up to 10mm² are acceptable and Terminal screws should be tightened to between 1.2 and 2 N·m.
관련된 링크들
- Siemens Residual Current Circuit Breaker with Overload Protection, 13 A Current Rating, 1-Pole, 30 mA Trip Sensitivity,
- Siemens Residual Current Circuit Breaker with Overload Protection, 13 A Current Rating, 2-Pole, 30 mA Trip Sensitivity,
- Siemens Residual Current Circuit Breaker with Overload Protection, 2 A Current Rating, 2-Pole, 30 mA Trip Sensitivity,
- Siemens Residual Current Circuit Breaker with Overload Protection, 16 A Current Rating, 1-Pole, 30 mA Trip Sensitivity,
- Siemens Residual Current Circuit Breaker with Overload Protection, 10 A Current Rating, 1-Pole, 30 mA Trip Sensitivity,
- Siemens Residual Current Circuit Breaker with Overload Protection, 6 A Current Rating, 2-Pole, 30 mA Trip Sensitivity,
- Siemens Residual Current Circuit Breaker with Overload Protection, 10 A Current Rating, 2-Pole, 30 mA Trip Sensitivity,
- Siemens Residual Current Circuit Breaker with Overload Protection, 4 A Current Rating, 1-Pole, 30 mA Trip Sensitivity,