Siemens IWLAN Series Communication Module for Use with Communication Module

Subtotal (1 unit)*

₩2,261,280.00

Add to Basket
수량 선택 또는 입력
재고있음
  • 3 개 단위 배송 준비 완료
더 자세한 내용이 필요하신가요? 필요한 수량을 입력하고 '배송일 확인'을 클릭하면 더 많은 재고 및 배송 세부정보를 확인하실 수 있습니다.
수량
한팩당
1 +₩2,261,280.00

* 참고 가격: 실제 구매가격과 다를 수 있습니다

RS 제품 번호:
211-9078
Distrelec 제품 번호:
301-24-590
제조사 부품 번호:
6GK5761-1FC00-0AA0
제조업체:
Siemens
제품 정보를 선택해 유사 제품을 찾기
모두 선택

브랜드

Siemens

Accessory Type

Communication Module

Product Type

Communication Module

Series

IWLAN

For Use With

Communication Module

IP Rating

IP20

Standards/Approvals

CSA, UL

Hazardous Area Certification

B, Class 1, D, Div 2, Group A, C

Supply Voltage

28.80V

COO (Country of Origin):
DE

Siemens IWLAN Series Communication Module, IP20, 28.80V Supply Voltage - 6GK5761-1FC00-0AA0


This communication module provides industrial wireless connectivity for demanding environments, offering single-radio access point functionality across 2.4GHz and 5GHz bands with support for IEEE 802.11a/b/g/h/n standards. Designed for integration into IWLAN networks, it supplies an RJ45 Ethernet Interface and an external R-SMA antenna connection for flexible deployment. The device operates from a DC Terminal Block and is intended for use where national approvals and hazardous-area installation rules apply.

Features and Benefits:


• 150 Mbit/s WLAN throughput for high-speed wireless transfer
• 100 Mbit/s Ethernet port enabling robust wired backbone connection
• 28.8 V supply for stable DC-powered industrial installations
• WPA2/802.11i security providing strong wireless access protection
• R-SMA external antenna port allowing flexible antenna placement

Applications


• Suitable for IWLAN access point deployment in factories
• Ideal for connecting mobile automation equipment wirelessly
• Used with control networks requiring industrial Ethernet bridging
• Can be used for wireless monitoring in Zone 2 enclosures
• Suitable for installations needing RJ45 device interfacing

What power connections does it use?


Power is supplied via a 3‑pole screw Terminal allowing DC input from the Terminal Block at 19.2 V or 28.8 V ranges and typical current draw is 0.15 A at 24 V.

How does it handle environmental conditions?


Operating ambient range is 0 to 55 °C with storage and transport rated -40 to +85 °C and up to 95% relative humidity at 25 °C without condensation.

Which management and protocols are supported?


It supports CLI and web-based management, SNMP v1/v2/v3, HTTP/HTTPS, Telnet, TFTP, LLDP, and NTP/SNTP time synchronisation.

What redundancy and network resilience features are available?


The unit supports STP/RSTP and MSTP protocols and offers forced roaming on IP or link failure for continuous connectivity.

How is hazardous-area use addressed?


For use in Zone 2 hazardous atmospheres it must be mounted inside an enclosure meeting at least IP54 to satisfy EN 50021 requirements.