Siemens 3UF7300 Series Digital I/O Module for Use with SIMOCODE

Subtotal (1 unit)*

₩488,220.00

Add to Basket
수량 선택 또는 입력
재고있음
  • 1 개 단위 배송 준비 완료
더 자세한 내용이 필요하신가요? 필요한 수량을 입력하고 '배송일 확인'을 클릭하면 더 많은 재고 및 배송 세부정보를 확인하실 수 있습니다.
수량
한팩당
1 +₩488,220.00

* 참고 가격: 실제 구매가격과 다를 수 있습니다

RS 제품 번호:
162-008
제조사 부품 번호:
3UF7300-1AU00-0AX0
제조업체:
Siemens
제품 정보를 선택해 유사 제품을 찾기
모두 선택

브랜드

Siemens

Accessory Type

Digital I/O Module

Product Type

Digital I/O Module

Series

3UF7300

For Use With

SIMOCODE

Hazardous Area Certification

No

Standards/Approvals

RoHS Directive, UL, UKCA, REACh Regulation, RCM, EAC, CE

Communication Protocol

I/O

Supply Voltage

110, 240V ac/dc

COO (Country of Origin):
DE

Siemens 3UF7300 Series Digital I/O Module, I/O Communication Protocol, For Use With SIMOCODE - 3UF7300-1AU00-0AX0


This digital I/O module provides four configurable digital inputs and two relay outputs for integration with motor-control logic blocks in SIMOCODE Basic units. It accepts a control supply of 110–240V AC/DC and is suitable for use in industrial automation panels where additional discrete signalling and switching are required.

Features & Benefits


• Four digital inputs enable extensive discrete signal acquisition
• Two monostable relay outputs provide isolated switching capability
• Relay NO contact current up to 6A at 50°C for control loads
• DC switching capacity of up to 2A at 24V for low-voltage circuits
• Surge resistance rated at 4000V to withstand transients
• IP20 enclosure and finger-safe touch protection for panel mounting

**Applications**


• Suitable for expanding discrete I/O on SIMOCODE Basic units
• Used for signalling motor states in industrial control cabinets
• Ideal for switching contactors and indicators in automation systems
• Can be used for interfacing remote sensors with central control
• Used with motor-protection logic where galvanic separation is required

What types of outputs are available and how are they configured?


The module provides two floating normally open relay contacts

their assignments can be mapped to control functions such as contactors or status signals and NC behaviour can be set via internal signal conditioning.

How should short-circuit protection be implemented per output?


Each output requires protection using gG fuse links (6A), fast‑acting fuses (10A), or miniature circuit‑breakers with specified characteristics such as C‑curve 1.6A for low prospective fault currents.

What environmental limits apply during operation?


Operational ambient temperature is between −25°C to +50°C with up to 95% relative humidity and compliance with IEC 60721 environmental categories for industrial conditions excluding condensation and salt mist.

How are electrical connections MADE and what conductor sizes are supported?


Removable terminals accept solid conductors up to 4 mm² or two conductors up to 2.5 mm², with recommended tightening torque of 0.8–1.2 N·m for secure terminations.

What electromagnetic immunity and emissions performance can be expected?


The unit meets IEC 60947‑1 immunity levels including 1kV burst and 2kV conductor‑earth surge, with CISPR 11 Class A emissions and field immunity to 10 V/m.