ABB System Pro M Compact S200 Circuit Breaker, 3+N-Pole, 25A, Type C, 440V ac AC, 110 V dc DC, 10 kA Breaking Capacity

현재 이용 불가
이 품목의 재입고 여부는 알 수 없으며 제조업체에서 단종되고 있습니다.
RS 제품 번호:
287-6358
Distrelec 제품 번호:
303-11-491
제조사 부품 번호:
2CDS253103R0254
제조업체:
ABB
제품 정보를 선택해 유사 제품을 찾기
모두 선택

브랜드

ABB

Number of Poles

3+N

Product Type

Circuit Breaker

Current Rating

25A

Tripping Characteristics

Type C

Rated AC Voltage

440V ac

Rated DC Voltage

110V dc

Breaking Capacity

10kA

Mount Type

DIN Rail

Range

System Pro M Compact

Series

S200

Terminal Type

Screw

IP Rating

IP40, IP20

Depth

69mm

Height

88mm

Standards/Approvals

IEC/EN 60898-1, IEC/EN 60947-2, UL1077

Width

70mm

Reset Actuator Type

Toggle

Tripping Mechanism

Electromechanic, Thermal

COO (Country of Origin):
DE

ABB S200 Series Circuit Breaker, 25A Current, 110V Rated DC Voltage - 2CDS253103R0254


This circuit-breaker is a Compact protective device designed for DIN-rail mounting to interrupt fault currents and protect electrical installations. It combines thermal and electromechanical trip elements to respond to overloads and short circuits, providing protection across both DC and AC circuits in control panels.

Features and Benefits:


• 10 kA breaking capacity limits fault energy and protects downstream equipment
• Type C tripping curve provides enhanced protection for mixed inductive loads
• 25 A rating supports mid-range current distribution requirements
• Screw terminals enable secure conductor connections under vibration
• Toggle reset offers quick manual restoration after trip events

Applications


• Suitable for three-phase systems requiring NEUTRAL protection
• Used with 110 Vdc control circuits in industrial
• Ideal for 440 Vac distribution in switchboards
• Used for Compact DIN-rail installations with limited panel space

How does the trip system handle both overloads and short circuits?


It uses a thermal element for long-duration overloads and an electromechanical element for Rapid fault interruption.

What Terminal connectivity is provided for field wiring?


Termination is by screw-type terminals designed for conventional conductor fastening.

Which ingress protection levels apply to this unit?


The enclosure meets IP40 for the front and IP20 for internal access, defining dust protection and finger-safe barriers.

Can it be mounted on standard DIN rails?


Yes, it is intended for DIN-rail mounting compatible with typical panel rails.

관련된 링크들