Eaton 400 A Fuse Holder, 3P-Pole for NH2 Fuse

Subtotal (1 unit)*

₩922,127.70

Add to Basket
수량 선택 또는 입력
제조사가 재고 비축중
  • 2026년 5월 25일 부터 배송 준비 완료
더 자세한 내용이 필요하신가요? 필요한 수량을 입력하고 '배송일 확인'을 클릭하면 더 많은 재고 및 배송 세부정보를 확인하실 수 있습니다.
수량
한팩당
1 +₩922,127.70

* 참고 가격: 실제 구매가격과 다를 수 있습니다

RS 제품 번호:
127-395
제조사 부품 번호:
183068 XNH2-FCL-S400-BT
제조업체:
Eaton
제품 정보를 선택해 유사 제품을 찾기
모두 선택

브랜드

Eaton

Product Type

Fuse Holder

Number of Poles

3

Body Material

Polyamide

IP Rating

IP10, IP20, IP2XC

Minimum Operating Temperature

-5°C

Compatible Fuse Size

NH2 Fuse

Maximum Operating Temperature

55°C

Standards/Approvals

IEC/EN 61439, RoHS

Series

XNH2

Terminal Type

Clamp

제외

COO (Country of Origin):
DE

Eaton xEffect Series Fuse Holder, 400A Current, 800V Voltage - 183068 XNH2-FCL-S400-BT


This fuse holder is a three-pole device designed to house NH2 fuse-links for use on busbar systems within industrial switchgear. It provides front-access actuation and box Terminal connections for heavy-copper conductors, enabling straightforward installation in panel and busbar arrangements where Visual fuse monitoring is required.

Features & Benefits


• Rated for 400A continuous current for high-current circuits
• Insulation withstands up to 800V AC for elevated system voltages
• Conditioned short-circuit rating 120 kA for fault tolerance
• Sliding inspection windows enable safe voltage verification
• Box terminals accept 95 to 300mm² single lugs for large conductors
• IP20 protection in service with IP10/IP2XC states during maintenance

Applications


• Suitable for industrial panel distribution with NH2 fuse-links
• Ideal for integration into 60mm busbar systems in switchgear
• Used with heavy-current feeders in manufacturing plants
• Suitable for front-mounting where Visual fuse indication is needed

What conductor sizes can I terminate at the box terminal?


Single cable lugs from 95mm² up to 300mm² are supported, while stranded cable ranges include 25mm² to 240mm² depending on Terminal configuration.

How does the device indicate a blown fuse?


It provides optical signalling of triggered fuse-links so an operator can identify a blown fuse from the front.

Which mechanical mounting orientations are permitted?


It can be mounted vertically or horisontally on busbars with a 60mm spacing.

What are the operating temperature limits for installation?


The ambient operating range is −25 °C to 55 °C for normal service conditions.