Alpha Wire Xtra-Guard 4 Performance Cable Control Cable, 2 Cores, 0.35mm² 22 AWG, Screened, 30 m, Black Thermoplastic

Subtotal (1 reel of 30 metres)*

₩793,435.50

Add to Basket
수량 선택 또는 입력
재고있음
  • 추가로 2026년 6월 05일 부터 4 개 단위 배송
더 자세한 내용이 필요하신가요? 필요한 수량을 입력하고 '배송일 확인'을 클릭하면 더 많은 재고 및 배송 세부정보를 확인하실 수 있습니다.
릴당
릴당
미터당*
1 +₩793,435.50₩26,447.85

* 참고 가격: 실제 구매가격과 다를 수 있습니다

RS 제품 번호:
884-0792
제조사 부품 번호:
45102 BK005
제조업체:
Alpha Wire
제품 정보를 선택해 유사 제품을 찾기
모두 선택

브랜드

Alpha Wire

Product Type

Control Cable

Series

Xtra-Guard 4 Performance Cable

Number of Cores

2

Conductor Material

Tin Copper Wire

Jacket Material

Thermoplastic Elastomer

Jacket Colour

Black

Screened/Unscreened

Screened

Outside Diameter

6.25mm

Cable Length

30m

Voltage

300V

Minimum Operating Temperature

-50°C

Maximum Operating Temperature

125°C

Standards/Approvals

UL, CSA, CE

Hazardous Area Certification

No

Cable CSA

0.35mm²

American Wire Gauge

22AWG

Fire Behaviour

FT1

Core Strands

7

Belden Xtra-Guard 4 Performance Cable Series Control Cable, 30m Cable Length, 2 Cores - 45102 BK005


This control cable is a screened, two-core assembly designed for industrial automation and electrical installations requiring robust signal integrity and high-temperature endurance. It combines tinned copper conductors and a thermoplastic elastomer jacket to perform in challenging environments while maintaining flexibility across a wide temperature span.

Features & Benefits


• 7-strand tinned copper conductors deliver improved corrosion resistance and conductivity
• Screen with drain and braid reduces electromagnetic interference on signal lines
• 300V rating supports typical control and instrumentation circuits
• FT1 fire behaviour permits limited flame propagation in confined spaces
• Temperature range of -50°C to 125°C enables operation in extreme conditions

**Applications**


• Suitable for factory automation signal runs where screening is required
• Ideal for control panels and equipment wiring in manufacturing plants
• Used with motion control systems requiring flexible cable routing
• Can be used for instrumentation links in harsh indoor environments

How is the cable shield constructed and terminated?


The shield comprises an aluminium/polyester/aluminium tape Plus a tinned copper braid with a tinned copper drain wire for straightforward termination to earth or chassis.

What insulation and jacket materials are used and their advantages?


Individual conductors are insulated with a nominal thermoplastic elastomer wall and the outer sheath is also TPE, offering sunlight resistance, flexibility and suitability for higher temperature ratings.

What mechanical handling limits should be observed?


The recommended minimum bend radius is 10x the cable diameter and maximum pull tension is 19.1 lb to avoid damage during installation.

Which approvals and standards apply to this cable?


It meets UL, CSA and CE-related specifications for AWM/PLTC usage, with RoHS compliance and specific sunlight-resistant classifications for selected colours.

How is identification printed on the sheath for inventory control?


The sheath legend includes the manufacturer's name and type designation along with a sequential footage marker to aid traceability.