Phoenix Contact QUINT-PS/3AC/24DC/40 Switch Mode DIN Rail Power Supply, 400V ac ac Input, 24V dc dc Output, 40A Output,
- RS 제품 번호:
- 665-7823
- 제조사 부품 번호:
- 2866802
- 제조업체:
- Phoenix Contact
모든 DIN Rail Power Supplies 열람하기
일시 품절-다음 입고 날짜는 14/06/2023 (일/월/년) 이며, 그 후 5-10영업일내 홍콩에서 발송. 정확한 입고 수량에 대한 문의는 krenquiry@rs-components.com 로 연락주세요.
단가 Each
₩1,201,070.50
수량 | 한팩당 |
1 + | ₩1,201,070.50 |
- RS 제품 번호:
- 665-7823
- 제조사 부품 번호:
- 2866802
- 제조업체:
- Phoenix Contact
제정법과 컴플라이언스
제품 세부 사항
QUINT POWER Single and Three Phase Power Supplies
QUINT POWER generation maximizes the availability of your plant. With some featuring the SFB technology (Selective Fusebreaking Technology), the 6-times nominal current for 12 ms, can be the first time standard circuit breakers reliable and quick trigger. Faulty current paths are selectively shut down, the error is limited and important Plant parts remain in operation.
Features and benefits:
Selective Fusebreaking Technology (CRC Technology)
Worldwide use through wide-range input for DC and AC networks
Reliable start difficult loads with static power reserve POWER BOOST
High reliability through high MTBF> 500,000 h, long power failure bridging times > 20 ms, high voltage to 300 Vac
Preventive function monitoring DC-OK by professional signaling
Slim design
Conformal coating for extreme environments (Some models)
Worldwide use through wide-range input for DC and AC networks
Reliable start difficult loads with static power reserve POWER BOOST
High reliability through high MTBF> 500,000 h, long power failure bridging times > 20 ms, high voltage to 300 Vac
Preventive function monitoring DC-OK by professional signaling
Slim design
Conformal coating for extreme environments (Some models)
How do I wire a DIN rail power supply?
The QUINTPOWER power supply unit's feature terminal blocks on both the top & bottom of the unit. You'll need to strip 7mm length from your cable and insert it into the terminal blocks. A simple screw connection (M4 screw) will then lock your cable into the terminal block, providing an output or input connection. However, please follow all manafactuer installation instructions.
What are DIN-rail power supplies used for?
Typically these power supplies are mounted into cabinets and are used in industrial circumstances. They can be used for automation, machinery or any project that has modules that are mounted on DIN-rails.
Note
665-7766, 665-7769, 665-7794 and 665-7790 do not feature SFB technology
Approvals
UL/C-UL Recognised (UL 60950), UL/C-UL Listed (UL 508) approved, CSA, CB, ABS
사양
속성 | 값 |
Output Voltage | 24V dc |
Output Current | 40A |
AC or DC Input Voltage | ac |
AC or DC Output Voltage | dc |
Input Voltage | 400V ac |
Power Rating | 960W |
Electrical Phase | 3 |
Number of Outputs | 1 |
Mounting Type | DIN Rail Mount |
Type | Switch Mode |
Width | 96mm |
Height | 130mm |
Series | QUINT-PS/3AC/24DC/40 |
Depth | 130mm |
Maximum Temperature | +70°C |
Ripple And Noise | 40mV Pk-Pk |
MTBF | 900000h |
Efficiency | >94% |
Minimum Temperature | -25°C |
일시 품절-다음 입고 날짜는 14/06/2023 (일/월/년) 이며, 그 후 5-10영업일내 홍콩에서 발송. 정확한 입고 수량에 대한 문의는 krenquiry@rs-components.com 로 연락주세요.